You have no items to compare.
Hi, Dear! Welcome to our online store...
DSA-AT thermocouple input barrier (analog type)
1 in 1 out, 1 in 2 out. Thermocouple signal, intrinsically safe input. Terminal supply or DIN rail power supply is available.
· The DSA-AT Thermocouple Input Barrier is a temperature-transfer isolation barrier that converts the field thermocouple millivolts to a standard current. The thermocouple input isolation safety barrier is composed of analog circuits, has the advantages of no resolution error, no sampling period error, and has high reliability, no crash risk and other important characteristics.
· Output signal 4~20mA or 0~20mA
· This product requires a separate DC power supply. Voltage-type magnetic isolation between power supply-input-output.
Model /Selection Table:
Option |
Model and code |
Description |
Basic model |
DSA-AT |
Thermocouple input barrier |
Channel form |
11 |
1 in 1 out |
12 |
1 in 2 out |
|
Input signal |
-T |
Thermocouple (K, E, S, B, T) |
-Z |
Other special thermocouples |
|
Output signal |
A |
4~20mA |
B |
0~20mA |
|
Z |
Special order |
|
Power supply voltage |
-V1 |
Power supply (terminal) 20 ~ 32VDC |
-V2 |
Power supply (rail) 20~32VDC (special power supply DIN rail required) |
|
Service Code |
-QC9A |
Product Service Code |
Selection example
Example 1: DSA-AT11-TA-V1-QC9A ...... (1 input and 1 output, thermocouple input safety barrier, output signal 4~20mA, terminal power supply 20~32VDC)
Example 2: DSA-AT12-TA-V2-QC9A ...... (1 in 3 out, thermocouple input safety barrier, output signal 4~20mA, rail supply 20~32VDC)
Example 3: DSA-AT11-TZ-V1-QC9A ...... (1 input and 1 output, thermocouple input safety barrier, output signal 1~5V, rail supply 20~32VDC)
Indication
1. Please indicate the signal type and range when ordering.
2. If you select a rail-powered product, please order a dedicated DIN rail.
Optional accessories
Dedicated power supply DIN rail: PSDR-3000 series
Technical data:
Size:
Width |
14.5mm |
Height |
102.6mm |
Depth |
124mm |
Housing Material / Color |
PC(Polycarbonate)+PPT Material / Black Gray |
Protection level |
IP20 |
Environmental conditions:
Ambient temperature |
-20~+60℃ |
Ambient temperature (storage or operation) |
-40~+80℃ |
Ambient humidity (operation) |
5~95%RH (no condensation) |
Input (intrinsically safe):
Input signal |
K, E, S, B and other thermocouples |
Temperature measurement range |
depends on sensor type |
Output:
Current output |
4~20mA ; 0~20mA |
Maximum current output |
22mA(±1mA) |
Current Output Load |
Adaptive Load 0~300Ω (factory default) |
Output ripple |
<10mV p-p |
Output status when input overload or open circuit |
Output current <3.5mA (lower limit) or >21mA (upper limit) |
Power supply:
Rated supply voltage |
24VDC |
Power supply voltage range |
20~30VDC |
Maximum current consumption |
<25mA (1 in 1 out); <40mA (1 in 2 out) |
General parameters:
Standard accuracy |
typical value±0.1%FS |
Zero migration range |
-10~100mV |
Range migration range |
3.8~100mV |
Output resolution |
<3.8~100mV range, 1μA |
Load change effect |
±2μA |
Thermocouple input, cold junction compensation error |
±0.5~1℃ (compensation range -15~+75℃) |
Temperature drift |
· -10~35 mV range: 0.0005% or 0.6μV (whichever is larger) |
Power-on or storage time drift |
±2μA (180 days) |
Response time |
<10ms |
Power-on stabilization time |
<1s |
Maximum withstand voltage |
Input-output-power supply: 2500V AC RMS / 1 minute |
Protection parameters |
· Power-on shock protection, power-on slow start >20ms · Distribution protection, distribution output clamp current 28mA (±4mA) B. Input-output-power supply can withstand 2500V RMS/1 minute without damage. C. The short circuit or open circuit formed by the misconnection of the terminal is not damaged. |
Electromagnetic compatibility (EMC) |
in accordance withIEC 61326-1 (GB/T 18268) , IEC 61326-3-1 |
LED backlight indication |
Power on, the product model on the panel is clearly visible through the LED backlight perspective, white. |
Applicable occasions |
Installed in a safe place, it can be connected to intrinsically safe equipment in Zone 0, Zone 1, Zone 2; IIC, IIB, IIA; T4~T6 hazardous areas |
Field device suitable for connection |
Thermocouple temperature sensor |
Mounting method |
Horizontal or vertical mounting, can be snapped onto standard 35mm DIN rail (or dedicated busbar backplane powered DIN rail) |
Wiring parameters:
Rigid conductor cross section (min/max) |
0.5mm²/2.5mm² |
Flexible conductor cross section (min/max) |
0.5mm²/2.5mm² |
Minimum Conductor Cross Section (AWG)) |
24 |
Maximum Conductor Cross Section (AWG) 14 |
14 |
Stripping length |
7mm |
Connection type |
M3 screw fastening connection |
Screw torque |
Up to0.6Nm |
Explosion-proof parameters:
Maximum safety voltage (Um) |
250VAC/DC |
Maximum output voltage (Uo) |
7.2VDC |
Maximum output current (Io) |
8.68mA |
Maximum output power (Po) |
15.62mW |
Maximum external inductance (Lo) |
5mH |
Maximum external capacitance (Co) |
6μF |
Certification/Standards:
CE certification |
in line with CE standards |
National Explosion-proof Electrical Product Quality Supervision and Inspection Center (CQST) certification |
[Ex ia Ga] IIC conforms to GB 3836.1, GB 3836.4, GB 3836.20 |
Product drawing / terminal wiring diagram: