You have no items to compare.
Hi, Dear! Welcome to our online store...
SKS-PD5 DC Power Line Surge Protector (5A)
· Designed to protect DC power lines below 5A, it can be applied to various 24V or 12VDC power lines, relays and solenoid valve drive lines.
· Designed to protect DC power lines, it can be applied to various 24V or 12VDC power lines, relays and solenoid valve drive lines;
· Only 7.2mm ultra-thin form factor, saving space;
· Adopt serial multi-level protection circuit design;
· bleeder current up to 10KA (8/20μs);
· 35mm DIN rail mounting;
· There is a special grounding terminal or metal rail grounding;
Model/Selection Table:
Option |
Model and code |
Description |
Basic model |
SKS-PD5 |
DC power line (5A or less) |
Line voltage |
24 |
24VDC |
12 |
12VDC |
|
When ordering |
Technical data:
Name |
Symbol |
Parameter |
Structure |
|
Integrated thin card-mounted structure |
Wiring |
|
Wiring European terminal connection,0.5~2.5mm² |
Housing material |
|
PC+ABS flame retardant material |
Flame retardant rating |
|
UL94 V-2 |
Enclosure protection class |
|
IP20 (IEC60529) |
|
|
Line voltage“24” (line voltage“12”) |
Rated operating voltage |
UN |
24V (12V) |
Maximum working voltage |
UC |
30V (15V) |
Maximum line current(8/20 μs) |
IL |
5A |
Maximum discharge current(8/20 μs) |
Imax |
10KA |
Nominal discharge current(8/20 μs) |
ISN |
3KA |
Lightning impulse current (10/350 μs) |
Iimp |
1.5KA |
Voltage protection level@1KV/μs |
Up |
<40V (30V) |
Line resistance |
|
≤0.5Ω |
Maximum leakage current |
|
1μA |
Response time |
|
<1ns |
Insertion loss |
|
-0.5dB |
Test category |
|
C1、C2、D1 |
Mounting method |
|
35mm DIN standard rail card mounting (TH35-7.5 thickness 1mm) |
Working environment temperature |
|
-40~+80℃ |
Working environment humidity |
|
5%~95% RH |
Dimensions(W×H×D) |
|
7.2×96.5×95.5 (mm²) |
Weight |
|
About 80g |
Application and wiring: