XS-AT Thermocouple Input Isolator (Analog)
· 1 in 1 out, 1 in 2 out. Thermocouple signal input. The output signal is 4~20mA or 0~20mA. Terminal supply or DIN rail power supply is available.
· The XS-AT Thermocouple Input Isolator is a temperature transmitter that converts field thermocouple millivolts into a standard current signal. The product is composed of analog circuits, with no resolution error, no sampling period error, etc. It also has important characteristics such as high reliability and no crash risk.
· Output signal 4~20mA or 0~20mA
· This product requires a separate DC power supply. Voltage-type magnetic isolation between power supply-input-output.
Model / selection table:
Option |
Model and code |
Description |
Basic model |
XS-AT |
Thermocouple input signal isolator |
Channel form |
11 |
1 in 1 out |
12 |
1 in 2 out |
|
Input signal |
-T |
Thermocouple (K , E , S , B , T) |
-Z |
Other special thermocouples |
|
Output signal |
A |
4~20mA |
B |
0~20mA |
|
Z |
Special order |
|
Power supply voltage |
-V1 |
Power supply (terminal) 20~32VDC |
-V2 |
Power supply (rail) 20~32VDC (special power supply DIN rail required) |
|
Service Code |
-QC9A |
Product Service Code |
Selection example |
Technical data:
Size:
Width |
14.5mm |
Height |
102.6mm |
Height |
100mm |
Housing Material / Color |
PC (Polycarbonate) + PPT Material / Black Gray |
Protection level |
IP20 |
Environmental conditions:
Ambient temperature |
-20~+60℃ |
Ambient temperature (storage or operation) |
-40~+80℃ |
Ambient humidity (operation) |
5~95%RH (no condensation) |
Input:
Input signal |
K,E,S,B and other thermocouples |
Temperature measurement range |
Depends on sensor type |
Output:
Current output |
4~20mA ; 0~20mA |
Maximum output current |
22mA(±1mA) |
Current Output Load |
Adaptive Load 0~300Ω (factory default) |
Output ripple |
<10mV p-p |
Output status when input overload or disconnection |
Output current <3.5mA (lower limit) or >21mA (upper limit) |
Power supply:
Rated supply voltage |
24VDC |
Power supply voltage range |
20~32VDC |
Maximum current consumption |
<25mA (1 in 1 out); <40mA (1 in 2 out) |
General parameters:
Standard accuracy |
Typical values±0.1%FS |
Zero migration range |
-10~100mV |
Range migration range |
3.8~100mV |
Output resolution |
<3.8~100mV range, 1μA |
Load change effect |
±2μA |
Thermocouple input cold junction compensation error |
±0.5~1°C (compensation range -15~+75°C) |
Temperature drift |
· -10~35mV range: 0.0005% or 0.6μV (whichever is larger) |
Power-on or storage time drift |
±2μA (180days) |
Response time |
<10ms |
Power-on stabilization time |
<1s |
Maximum withstand voltage |
Input-output-power supply: 2500V AC RMS / 1 minute |
Protection parameters |
· Power-on shock protection, power-on slow start >20ms |
Electromagnetic compatibility (EMC) |
In accordance with IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
LED indication |
Green LED (power indication) |
Field device suitable for connection |
Thermocouple temperature sensor |
Mounting method |
Horizontal or vertical mounting, can be mounted on standard 35mm DIN rail (or dedicated busbar backplane powered DIN rail) |
Wiring parameters:
Rigid conductor cross section (min/max) |
0.5mm²/2.5mm² |
Flexible wire cross section (min/max) |
0.5mm²/2.5mm² |
Minimum wire cross section (AWG) |
24 |
Maximum wire cross section (AWG) |
14 |
Stripping length |
7mm |
Connection type |
M3 screw fastening connection |
Crew torque |
up to 0.6Nm |