XS-PI/PD/II Power distribution or current input isolator

· 1 in 1 out, 1 in 2 out, 2 in 2 out. Distribution voltage ≥17V (at 20mA). 0/4~20mA input. 0/4~20mA output. HART passed. Terminal supply or DIN rail power supply is available.

· The XS-PI (PD, II) is designed to be connected to a field transmitter or current source to provide power distribution to the field transmitter and to accept current signal input from the transmitter. Current source signal input can also be accepted separately. After isolation, interference suppression, etc., output standard current signals to the control system or other instruments.
· Output signal 4~20mA or 0~20mA.
· This product requires a separate DC power supply. Voltage-type magnetic isolation between power supply-input-output.

 

Model / selection table:

     Option

    Model and code

     Description

     Basic model

    XS-PI

     Power distribution or current input isolator

    XS-PD

    Dual channel, power distribution isolator (only suitable for channel type 2 in 2 out options)

    XS-II

    Dual channel, current signal isolator (only suitable for channel type 2 in 2 out options)

     Special function

        H

     HART pass (only for the basic model XS-PI option)

        P

     When P 20mA, the high distribution voltage is ≥22V (suitable for the model XS-PI or XS-PD option. If the code “P ” is not selected, the factory default distribution voltage is ≥17V)

        F

     Input line fault alarm

   

     Default, no special features

     Channel form

        11

     1 in 1 out

        12

     1 in 2 out

        22

     2 in 2 out     (optional for basic model XS-PD or XS-II)

     Input signal

        -A

     4~20mA or 0~20mA

     Output signal

         A

     4~20mA or 0~20mA  (1 to 1 corresponds to the input signal)

         Z

     Special order

     Power supply voltage

       -V1

     Power supply (terminal) 2032VDC

       -V2

     Power supply (rail) 2032VDC (special power supply DIN rail required)

     Service Code

    -QC9A

     Product Service Code

   Selection example 
   Example 1: XS-PIH11-AA-V1-QC9A 
      ...... (1 in 1 out, power distribution or current input isolator, HART pass, current signal 0/4~20mA, terminal power supply 20~32VDC) 
   Example 2: XS-PIPF12-AA-V1-QC9A 
      ...... (1 in 2 out, power distribution or current input isolator, high power distribution, line fault alarm, current signal 0/4~20mA, terminal power supply 20~32VDC) 
   Example 3: XS-PD22-AA-V1-QC9A ...... (2 in 2 out, power distribution input isolator, current signal 0/4~20mA, terminal power supply 20~32VDC)
   Example 4: XS-II22-AA-V2-QC9A ...... (2 in 2 out, current input isolator, current signal 0/4~20mA, rail supply 20~32VDC) 
   Optional accessories 
   Dedicated power supply DIN rail: PSDR-3000 series

 

Technical data:

Size:

     Width

    14.5mm

     Height

    102.6mm

     Height

    100mm

     Housing Material / Color

    PC (Polycarbonate) + PPT Material / Black Gray 

     Protection level  

    IP20

 

Environmental conditions:

    Ambient temperature

    -20~60℃

    Ambient temperature (storage or operation)

    -40~80℃

    Ambient humidity (operation)

    5~95RH (no condensation)

 

Input:

   Input current

    4~20mA ;  0~20mA

   Input impedance

    25Ω

   Distribution voltage supplied to the transmitter

    Factory default ≥17V (at20mA)

 

Output:

   Current output

    4~20mA ;  0~20mA

   Transmission characteristics

    1 to 1 corresponds to the input signal 

   Current output load

    Adaptive load 0~300Ω

   Output ripple

    <10mV p-p

   Output status when input overload or open circuit fault

    · Input overload: Output current ≥22mA
    · Input open circuit: output current 2mA

 

Power supply:

    Rated supply voltage

    24VDC

    Power supply voltage range

    20~32VDC

    Maximum current consumption

    <40mA (1 in 1 out); <50mA (1 in 2 out);

    <70mA (dual channel power isolator);
    <45mA (dual channel current signal isolator) 

 

General parameters:

    Standard accuracy

    Typical values±0.1%FS

    Temperature drift

    <±1μA/10℃

    Power-on or storage time drift

    ±2μA (180days)

    Load change effect

    ±2μA

    Response time

    <10ms

    Power-on stabilization time

    <1s

    Electrical isolation

    Input-output-power supply: 2500V AC RMS / 1 minute

    Protection parameters

    · Power-on shock protection, power-on slow start >20ms
    · Distribution protection, distribution output clamp current 28mA (±4mA)
    · Reverse power supply protection, reverse voltage -30V
    · Output protection, output clamp current 25mA (typical)
    · Port misconnection and surge protection:
       A. The power-input-output between the two ports of the self-loop can withstand the external loop voltage <±24V.
       B. Input-output-power supply can withstand 2500V RMS/1 minute without damage.
       C. The short circuit or open circuit formed by the misconnection of the terminal is not damaged.

    Electromagnetic compatibility (EMC)

    In accordance with IEC 61326-1 (GB/T 18268), IEC 61326-3-1

    LED indication

    Green LED (power indication)

    Applicable occasions

    Installed in a safe place, can be connected with intrinsically safe equipment in Zone 0, Zone 1, Zone 2; IIC, IIB, IIA; T4~T6 hazardous areas

    Field device suitable for connection

    Transmitter or current source signal

    Mounting method

    Horizontal or vertical mounting, can be mounted on standard 35mm DIN rail (or dedicated busbar backplane powered DIN rail)

 

Wiring parameters:

   Rigid conductor cross section (min/max)

    0.5mm²/2.5mm²

   Flexible wire cross section (min/max)

    0.5mm²/2.5mm²

   Minimum wire cross section (AWG)

    24

   Maximum wire cross section (AWG)

    14

   Stripping length

    7mm

   Connection type

    M3 screw fastening connection

   Crew torque

    up to 0.6Nm

 

Certification/standards:

    CE certification

    Meet CE standards

 

Product diagram / terminal wiring diagram:

 

           

Product Image Details

XS-PI/PD/II Power distribution or current input isolator 1

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

Only registered users can write reviews. Please Log In or Register

Product Questions

  • Submit your question to our community.


Our customers love us

  • High Quality With Global Standards.
  • Convenient and friendly customer service.
  • Fast and safe shipping around the globe.
  • Free Shipping Worldwide - Each Order, and no any tax!