XS-RTD RTD Input Isolator (Analog)
· 1 in 1 out, 1 in 2 out. Thermal resistance signal input. The output signal is 4~20mA or 0~20mA. Terminal supply or DIN rail power supply is available.
· XS-RTD Thermistor Input Isolator is a temperature transmitter that converts the field RTD resistance to a standard current signal. The RTD temperature transmitter is composed of analog circuit, has the advantages of no resolution error, no sampling period error, and also has important characteristics such as high reliability and no risk of crash.
· Output signal 4~20mA or 0~20mA
· This product requires a separate DC power supply. Voltage-type magnetic isolation between power supply-input-output.
Model / selection table:
Option |
Model and code |
Description |
Basic model |
XS-RTD |
Thermal resistance input isolator |
Channel form |
11 |
1 in 1 out |
12 |
1 in 2 out |
|
Input signal |
-R |
Thermal resistance (Pt100, Cu50) |
-Z |
Other special thermal resistance |
|
Output signal |
A |
4~20mA |
B |
0~20mA |
|
Z |
Special order |
|
Power supply voltage |
-V1 |
Power supply (terminal) 20~32VDC |
-V2 |
Power supply (rail) 20~32VDC (special power supply DIN rail required) |
|
Service Code |
-QC9A |
Product Service Code |
Selection example |
Technical data:
Size:
Width |
14.5mm |
Height |
102.6mm |
Height |
100mm |
Housing Material / Color |
PC (Polycarbonate) + PPT Material / Black Gray |
Protection level |
IP20 |
Environmental conditions:
Ambient temperature |
-20~+60℃ |
Ambient temperature (storage or operation) |
-40~+80℃ |
Ambient humidity (operation) |
5~95%RH (no condensation) |
Input:
Input signal |
Pt100,Cu50 and other thermal resistance |
Temperature measurement range |
Depends on sensor type |
Output:
Current output |
4~20mA ;0~20mA |
Maximum output current |
22mA(±1mA) |
Current Output Load |
Adaptive Load 0~300Ω (factory default) |
Output ripple |
<10mV p-p |
Output status when input overload or disconnection |
Output current <3.5mA (lower limit) or >21mA (upper limit) |
Power supply:
Rated supply voltage |
24VDC |
Power supply voltage range |
20~32VDC |
Maximum current consumption |
<35mA (1 in 1 out); <60mA (1 in 2 out) |
General parameters:
Standard accuracy |
Typical values±0.1%FS |
Zero migration range |
0~385Ω |
Range migration range |
12.8~400Ω |
Output resolution |
12.8Ω~400Ω range, 1μA |
Load change effect |
±2μA |
Temperature drift |
Typical values are 0.0015% or 4mΩ of the input maximum (whichever is greater) |
Power-on or storage time drift |
±2μA (180days) |
Response time |
<10ms |
Power-on stabilization time |
<1s |
Maximum withstand voltage |
Input-output-power supply: 2500V AC RMS / 1 minute |
Protection parameters |
· Power-on shock protection, power-on slow start >20ms |
Electromagnetic compatibility (EMC) |
In accordance with IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
LED indication |
Green LED (power indication) |
Field device suitable for connection |
Thermal resistance temperature sensor |
Mounting method |
Horizontal or vertical mounting, can be mounted on standard 35mm DIN rail (or dedicated busbar backplane powered DIN rail) |
Wiring parameters:
Rigid conductor cross section (min/max) |
0.5mm²/2.5mm² |
Flexible wire cross section (min/max) |
0.5mm²/2.5mm² |
Minimum wire cross section (AWG) |
24 |
Maximum wire cross section (AWG) |
14 |
Stripping length |
7mm |
Connection type |
M3 screw fastening connection |
Crew torque |
up to 0.6Nm |
Certification/standards:
CE certification |
Meet CE standards |
Product diagram / terminal wiring diagram: