XSA-AO output safety barrier
· 1 in 1 out, 2 in 2 out. 0/4~20 mA intrinsically safe output. Support for HART adoption. Terminal supply or DIN rail power supply is available.
· XSA-AO is suitable for the connection between the control system output signal and the on-site intrinsically safe circuit. After isolation, the standard DC signal is output to intrinsically safe equipment (such as valve controller and electrical converter) in the hazardous area of the site.
· Input signal 4~20mA or 0~20mA. The output signal is 4~20mA or 0~20mA.
· Support for HART pass (optional).
· This product requires a separate DC power supply. Voltage-type magnetic isolation between power supply-input-output.
Model /Selection Table:
Option |
Model and code |
Description |
Basic model |
XSA-AO |
Output barrier |
Special function |
H |
HART pass (only suitable for channel type 1 in 1 out option) |
|
Default, no special features |
|
Channel form |
11 |
1 in 1 out |
22 |
2 in 2 out |
|
Input signal |
-A |
4~20mA or 0~20mA |
Output signal |
A |
4~20mA or 0~20mA (1 to 1 corresponds to the input signal) |
Power supply voltage |
-V1 |
Power supply (terminal) 20 ~ 32VDC |
-V2 |
Power supply (rail) 20~32VDC (special power supply DIN rail required) |
|
Service Code |
-QC9A |
Product Service Code |
Selection example |
Technical data:
Size:
Width |
14.5mm |
Height |
102.6mm |
Depth |
100mm |
Housing Material / Color |
PC(Polycarbonate)+PPT Material / Black Gray |
Protection level |
IP20 |
Environmental conditions:
Ambient temperature |
-20~+60℃ |
Ambient temperature (storage or operation) |
-40~+80℃ |
Ambient humidity (operation) |
5~95%RH (no condensation) |
Input:
Input Current |
4~20mA ; 0~20mA |
Input resistance |
≥25Ω |
Output(intrinsically safe):
Current output |
4~20mA ; 0~20mA |
Transmission characteristics |
1 to 1 corresponds to the input signal |
Current output load |
adaptive load 0~550Ω |
Output ripple |
<10mV p-p |
Input state when output open circuit fault |
<1mA |
Power supply:
Rated supply voltage |
24VDC |
Power supply voltage range |
20~32VDC |
Maximum current consumption |
<45mA(1 in 1 out);<75mA(2 in 2 out) |
General parameters:
Standard accuracy |
Typical value±0.1%FS |
Temperature drift |
<±1μA/10℃ |
Power on or storage time drift |
±2μA (180天) |
Load change impact |
±2μA |
Response time |
<10ms |
Power-on stabilization time |
<1s |
Electrical isolation |
Input-output-power supply: 2500V AC RMS / 1 minute |
Protection parameters |
· Power-on shock protection, power-on slow start >20ms · Distribution protection, distribution output clamp current 28mA (±4mA) B. Input-output-power supply can withstand 2500V RMS/1 minute without damage. C. The short circuit or open circuit formed by the misconnection of the terminal is not damaged. |
Electromagnetic compatibility (EMC) |
in accordance with IEC 61326-1 (GB/T 18268) , IEC 61326-3-1 |
LED indication |
Green LED (power indication) |
Applicable occasions |
Installed in a safe place, can be connected with intrinsically safe equipment in Zone 0, Zone 1, Zone 2; IIC, IIB, IIA; T4~T6 danger zone |
Field device suitable for connection |
On-site intrinsic safety equipment such as I/P converters, control valves, and indicators |
Mounting method |
Horizontal or vertical mounting, can be mounted on standard 35mm DIN rail (or dedicated busbar backplane powered DIN rail) |
Explosion-proof parameters:
Maximum safety voltage (Um) |
250VAC/DC |
Maximum output voltage (Uo) |
24VDC |
Maximum output current (Io) |
151mA |
Maximum output power (Po) |
0.91W |
Maximum external inductance (Lo) |
1.1mH |
Maximum external capacitance (Co) |
0.09μF |
Certification/Standards:
CE certification |
Meet CE standards |
National Explosion-proof Electrical Product Quality Supervision and Inspection Center (CQST) certification |
[Ex ia Ga] IIC conforms to GB 3836.1, GB 3836.4, GB 3836.20 |
Product drawing / terminal wiring diagram: