You have no items to compare.
Hi, Dear! Welcome to our online store...
XSA-PI (PD, II) power distribution or current input barrier
· 1 in 1 out, 1 in 2 out, 2 in 2 out. 0/4~20mA intrinsically safe input. Distribution voltage ≥16V (at 20mA). 0/4~20mA output. HART passed. Terminal supply or DIN rail power supply is available.
· The XSA-PI (PD, II) is designed to be connected to a transmitter or current source in a hazardous area on site, to provide electrical distribution to the field transmitter, and to accept current signal input from the transmitter. Current source signal input can also be accepted separately. After isolation, interference suppression, etc., output standard current signals to the safety zone control system or other instruments.
· Output signal 4~20mA or 0~20mA.
· This product requires a separate DC power supply. Voltage-type magnetic isolation between power supply-input-output.
Model /Selection Table:
Option |
Model and code |
Description |
Basic model |
XSA-PI |
Power distribution or current input barrier |
XSA-PD |
Dual channel, power distribution input barrier (only adapts to channel type 2 in 2 out options) |
|
XSA-II |
Dual channel, current input barrier (only adapts to channel type 2 in 2 out options) |
|
Special function |
H |
HART pass (only for the basic model XSA-PI option) |
F |
Input line fault alarm |
|
|
Default, no special features |
|
Channel form |
11 |
1 in 1 out |
12 |
1 in 2 out |
|
22 |
2 in 2 out (adapt to the basic model XSA-PD or XSA-II option) |
|
Input signal |
-A |
4~20mA or 0~20mA |
Output signal |
A |
4~20mA or 0~20mA (1 to 1 corresponds to the input signal) |
Z |
Special order |
|
Power supply voltage |
-V1 |
Power supply (terminal)20~32VDC |
-V2 |
Power supply (rail) 20~32VDC (special power supply DIN rail required) |
|
Service Code |
-QC9A |
Product Service Code |
Selection example Example 2: XSA-PIF12-AA-V1-QC9A...... (1 in 2 out, power distribution or current input safety barrier, with line fault alarm, current signal 0/4~20mA, terminal power supply 20~32VDC) Example 3: XSA-PD22-AA-V1-QC9A ...... (2 in 2 out, power distribution input safety barrier, current signal 0/4~20mA, terminal power supply 20~32VDC Dedicated power supply DIN rail: PSDR-3000 series |
Technical data:
Size:
Width |
14.5mm |
Height |
102.6mm |
Depth |
100mm |
Housing Material / Color |
PC(Polycarbonate)+PPT Material / Black Gray |
Protection level |
IP20 |
Environmental conditions:
Ambient temperature |
-20~+60℃ |
Ambient temperature (storage or operation) |
-40~+80℃ |
Ambient humidity (operation) |
5~95%RH (no condensation) |
Input (intrinsically safe):
Input Current |
4~20mA ; 0~20mA |
Input resistance |
25Ω |
Distribution voltage supplied to the transmitter |
≥16V (at 20mA) |
Output:
Current output |
4~20mA ; 0~20mA |
Transmission characteristics |
1 to 1 corresponds to the input signal |
Current Output Load |
Adaptive Load 0~300Ω (factory default) |
Output ripple |
<10mV p-p |
Output status when input overload or open circuit fault |
· Input overload: Output current ≥22mA |
Power supply:
Rated supply voltage |
24VDC |
Power supply voltage range |
20~32VDC |
Maximum current consumption <50mA |
<50mA(1入1出);<70mA(1入2出); |
General parameters:
Standard accuracy |
Typical value±0.1%FS |
Temperature drift |
<±1μA/10℃ |
Power-on or storage time drift |
±2μA (180days) |
Load change effect |
±2μA |
Response time |
<10ms |
Power-on stabilization time |
<1s |
Electrical isolation: Input-output-power supply |
Input-output-power supply: 2500V AC RMS / 1 minute |
Protection parameters |
· Power-on shock protection, power-on slow start >20ms · Distribution protection, distribution output clamp current 28mA (±4mA) B. Input-output-power supply can withstand 2500V RMS/1 minute without damage. C. The short circuit or open circuit formed by the misconnection of the terminal is not damaged. |
Electromagnetic compatibility (EMC) |
in accordance with IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
LED backlight indication |
Power on, the product model on the panel is clearly visible through the LED backlight perspective, white. |
Applicable occasions |
Installed in a safe place, can be connected with intrinsically safe equipment in Zone 0, Zone 1, Zone 2; IIC, IIB, IIA; T4~T6 danger zone |
Field device suitable for connection |
Transmitter or current source signal |
Mounting method |
Horizontal or vertical mounting, can be mounted on standard 35mm DIN rail (or dedicated busbar backplane powered DIN rail) |
Wiring parameters:
Rigid conductor cross section (min/max) |
0.5mm²/2.5mm² |
Flexible conductor cross section (min/max) |
0.5mm²/2.5mm² |
Minimum Conductor Cross Section (AWG)) |
24 |
Maximum Conductor Cross Section (AWG) 14 |
14 |
Stripping length |
7mm |
Connection type |
M3 screw fastening connection |
Screw torque |
Up to0.6Nm |
Explosion-proof parameters:
Name |
Distributor operation (terminal 1-2) |
Isolator operation (terminals 2-3) |
Maximum output voltage (Uo) |
26.2VDC |
7.2VDC |
Maximum output current (Io) |
127mA |
3.7mA |
Maximum output power (Po) |
0.83W |
7mW |
Maximum external inductance (Lo) |
1.5mH |
2.4mH |
Maximum external capacitance (Co) |
0.05μF |
4μF |
Maximum safety voltage (Um) |
250VDC/AC |
Certification/Standards:
CE certification |
in line with CE standards |
National Explosion-proof Electrical Product Quality Supervision and Inspection Center (CQST) certification |
[Ex ia Ga] IIC conforms to GB 3836.1, GB 3836.4, GB 3836.20 |
Product drawing / terminal wiring diagram: