You have no items to compare.
Hi, Dear! Welcome to our online store...
XSA-RS485 communication barrier
· RS485 signal, intrinsically safe input. The RS485 signal is converted to an isolated RS485 (or RS232) signal. Terminal supply or DIN rail power supply is available.
· The XSA-RS485 communication barrier is used to convert the RS485 signal to the hazardous area of the field into an RS485 (or RS232) signal for transmission to the safe area to realize two-way communication between the dangerous area and the safe area. The product requires independent power supply and is isolated between the power supply-input-output.
· Hazardous area signal: RS485 digital signal.
· Safety zone signal: RS485 digital signal (or RS232 digital signal).
· Signal transmission rate: ≤ 56kbps. Transmission delay: ≤10uS.
· Small plug-in structure with 35mm DIN standard rail card mounting. Screw terminal, the wiring is fastened by M3 screw.
Model /Selection Table:
Option |
Model and code |
Description |
Basic model |
XSA-RS485 |
RS485 communication barrier |
Signal conversion |
-1 |
RS485 signal is converted to isolated RS485 signal |
-2 |
RS485 signal converted to isolated RS232 signal |
|
-Z |
Special order |
|
Power supply voltage |
-V1 |
Power supply (terminal) 20~32VDC |
-V2 |
Power supply (rail)20~32VDC |
|
Service Code |
-QC9A |
Product Service Code |
Selection example |
Technical data:
Size:
Width |
14.5mm |
Height |
102.6mm |
Depth |
100mm |
Housing Material / Color |
PC(Polycarbonate)+PPT Material / Black Gray |
Protection level |
IP20 |
Environmental conditions:
Ambient temperature |
-20~+60℃ |
Ambient temperature (storage or operation) |
-40~+80℃ |
Ambient humidity (operation) |
5~95%RH (no condensation) |
Input (intrinsically safe):
Signal Type |
RS485 Digital Signal |
Distribution voltage |
9V distribution voltage, current ≤100mA; 12V distribution voltage, current ≤60mA |
Power supply:
Signal type |
RS485 digital signal; RS232 digital signal |
Signal level rule |
Standard RS485 differential level; standard RS232 logic level |
Signal transmission rate |
≤56kbps |
Transmission delay |
≤10uS |
Power supply:
Rated supply voltage |
24VDC |
Power supply voltage range |
20~32VDC |
Maximum current consumption |
<130mA |
General parameters:
Electrical isolation |
Input-output-power supply: 2500V AC RMS / 1 minute |
Electromagnetic compatibility (EMC) |
in accordance with IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
LED status indication |
Green LED (power indication) |
Applicable occasions |
Installed in a safe place, can be connected with intrinsically safe equipment in Zone 0, Zone 1, Zone 2; IIC, IIB, IIA; T4~T6 danger zone |
Field device suitable for connection |
RS485 communication interface |
Mounting method |
Horizontal or vertical mounting, can be mounted on standard 35mm DIN rail (or dedicated busbar backplane powered DIN rail) |
Wiring parameters:
Rigid conductor cross section (min/max) |
0.5mm²/2.5mm² |
Flexible conductor cross section (min/max) |
0.5mm²/2.5mm² |
Minimum Conductor Cross Section (AWG)) |
24 |
Maximum Conductor Cross Section (AWG) 14 |
14 |
Stripping length |
7mm |
Connection type |
M3 screw fastening connection |
Screw torque |
Up to0.6Nm |
Explosion-proof parameters:
Maximum safety voltage (Um) |
250VAC/DC |
Maximum output voltage (Uo) |
8VDC |
Maximum output current (Io) |
90mA |
Maximum output power (Po) |
0.18W |
Maximum external inductance (Lo) |
3mH |
Maximum external capacitance (Co) |
5μF |
Certification/Standards:
CE certification |
in line with CE standards |
National Explosion-proof Electrical Product Quality Supervision and Inspection Center (CQST) certification |
[Ex ia Ga] IIC conforms to GB 3836.1, GB 3836.4, GB 3836.20 |