XSA-TP11BJ universal signal safety barrier-alarm setter

·  General purpose signal (RTD/TC/mV/mA), intrinsically safe input. Configurable settings. Compatible with HART. Analog signal output + relay contact alarm output.

·  The XSA-TP11BJ Alarm Setter adds a set of relay contacts to the alarm output of power distribution, current, thermal resistance, thermocouple, millivolt signal, and slip line resistance based on the general signal safety barrier. With isolation barrier function. It is a multi-functional intrinsically safe instrument that integrates signal alarm, signal transmission and isolation functions.

·  Switch power distribution, current, RTD, thermocouple, and millivolt signal input according to different wiring methods. The input signal type or range can be configured via software.

·  The output signal is 4~20mA, which can be extended to 0~20mA.

·  Relay contact alarm output, contact capacity 12VDC, 1A.

·  This product requires a separate DC power supply. Voltage-type magnetic isolation between power supply-input-output.

Model /Selection Table:

   Option

   Model and code

   Description

   Basic model

   XSA-TP11BJ

   Universal Signal Safety Guard-Alarm Setter

   Input signal

   -U

   General purpose signal (RTD , TC , mV , mA)

   Output signal

   A

   4~20mA

   B

   0~20mA

   Z

   Special order

   Power supply voltage

  -V1

   Power supply (terminal) 2032VDC

  -V2

   Power supply (rail) 2032VDC (Need to be equipped with dedicated power supply DIN rail)

   Service Code

  -QC9A

   Product Service Code

   Selection example 
   Example 1: XSA-TP11BJ-UA-V1-QC9A …….(General signal safety barrier---alarm setting device with display, 4~20mA output + one set of relay contact alarm output, terminal power supply 20~32VDC) 
   Example 2: XSA-TP11BJ-UA-V2-QC9A ……(General signal safety barrier---alarm setting device, 4~20mA output+set of relay contact alarm output, rail supply 20~32VDC)
   Indication
   1. Please indicate the signal type and range when ordering. Otherwise, it will be shipped according to the default setting: with power distribution, input signal 4~20mA, output signal 4~20mA. 
   2. If you select a rail-powered product, please order a dedicated DIN rail.  
   Optional accessories
    · Configuration software: CRFW-2000, CRFA-1904

    · Calibration interface: CR-2206, FAIF-1904 
    · Dedicated power supply DIN rail: PSDR-3000 series

Technical data:

Size:

    Width

   14.5mm

    Height

   102.6mm

    Depth

   100mm

    Housing Material / Color

   PC(Polycarbonate)+PPT Material / Black Gray

    Protection level

   IP20

 

Environmental conditions:

    Ambient temperature

   -20~60℃

    Ambient temperature (storage or operation)

   -40~80℃

    Ambient humidity (operation)

    5~95RH  (no condensation)

 

Input (intrinsically safe):

   Available Sensor Types(RTD

    Pt100, Cu50 and other thermal resistance

   Available sensor types(TC

    KESB and other thermocouples

   Temperature measurement range

    depends on sensor type

   Millivolt signal

    0~100mV

   Current signal

    4~20mA Or 0~20mA

   Distribution voltage to the transmitter

    ≥16V (at 20mA)

 

Output:

   Current output signal

    4~20mA ;  0~20mA

   Maximum current output signal

    22mA(±1mA)

   Current Output Load

    Adaptive Load 0~300Ω (factory default)

   Output ripple

    <10mV p-p

   Alarm output

    Relay contact

   Contact capacity

    12V1A

   Load Type

    Resistive Load

 

 Power supply:

   Rated supply voltage

    24VDC

   Power supply voltage range

    20~32VDC

   Maximum current consumption

    60mA  

 

 General parameters:

   Standard accuracy

    Typical value±0.1%FS

   Zero migration range

    -10~100mV or 0~385Ω

   Range migration range

    3.8~100mV or 12.8~400Ω

   Output resolution

    <3.8~100mV or 12.8Ω~400Ω range, 1μA

   Load change effect

    ±2μA

   Wire resistance

    Thermal resistance three-wire input (≤10Ω/line), <±0.005 %/Ω

   Thermocouple input, cold junction compensation error

    ±0.5~1℃ (compensation range-15~+75℃)

   Temperature drift

   · -10~35 mV range: 0.0005% or 0.6μV (whichever is larger) 
   · -10~75 mV range: 0.0005% or 1.2μV (take the larger one)
   · 10~400Ω range: 0.0015% or 4mΩ (whichever is larger)

   Power-on or storage time drift

    ±2μA (180 days)

   Response time

    <10ms

   Power-on stabilization time

    <1s

   Maximum withstand voltage

    Input-output-power supply: 2500V AC RMS / 1 minute

   Protection parameters

   · Output protection, output clamp current 22mA (typical)
   · Port misconnection and surge protection:
   A.The power-input-output between the two ports of the self-loop can withstand the external loop voltage <±24V.       

   B. Input-output-power supply can withstand 2500V RMS/1 minute without damage.       

   C. The short circuit or open circuit formed by the misconnection of the terminal is not damaged.

   Electromagnetic compatibility (EMC)

   in accordance with IEC 61326-1 (GB/T 18268) , IEC 61326-3-1

   LED indication

   Green LED (power indication)

   Applicable occasions

   Installed in a safe place, can be connected with intrinsically safe equipment in Zone 0, Zone 1, Zone 2; IIC, IIB, IIA; T4~T6 danger zone

   Field device suitable for connection

   Thermal resistance or thermocouple temperature sensor, millivolt signal, transmitter or current source signal

   Mounting method

   Horizontal or vertical mounting, can be mounted on standard 35mm DIN rail (or dedicated busbar backplane powered DIN rail)

 

Wiring parameters:

   Rigid conductor cross section (min/max)

    0.5mm²/2.5mm²

   Flexible conductor cross section (min/max)

    0.5mm²/2.5mm²

   Minimum Conductor Cross Section (AWG))

    24

   Maximum Conductor Cross Section (AWG) 14

    14

   Stripping length

    7mm

   Connection type

    M3 screw fastening connection

   Screw torque

    Up to0.6Nm

 

Explosion-proof parameters:

  Name

   Temperature converter operation (terminals 1-2-3)

   Isolator operation (terminal 1-2)

    Distributor Operation (terminals 1-4)

  Maximum output voltage (Uo)

    4.6VDC

    4.6VDC

    26.2VDC

  Maximum output current (Io)

    0.04A

    0.25A

    127mA

  Maximum output power (Po)

    0.046W

    0.345W

    0.83W

  Maximum external inductance (Lo)

    40mH

    0.7mH

    1.5mH

  Maximum external capacitance (Co)

    100μF

    100μF

    0.05μF

  Maximum safety voltage (Um)

    250VDC/AC

 

Certification/Standards:

  CE certification

    in line with CE standards

  Supervision and Inspection Center (CQST) certification

    [Ex ia Ga] IIC conforms to GB 3836.1GB 3836.4GB 3836.20

 

Product drawing / terminal wiring diagram:

           

Product Image Details

XSA-TP11BJ universal signal safety barrier-alarm setter 1

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.

  1. Be the first to review this product

Write Your Own Review

Only registered users can write reviews. Please Log In or Register

Product Questions

  • Submit your question to our community.


Our customers love us

  • High Quality With Global Standards.
  • Convenient and friendly customer service.
  • Fast and safe shipping around the globe.
  • Free Shipping Worldwide - Each Order, and no any tax!