· 1 in 1 out, 1 in 2 out, suitable for RTD or thermocouple temperature sensor, intrinsically safe input. The settings can be configured. 0/4~20mA output. Terminal supply or DIN rail power supply is available.
· XSA-ZT is suitable for the input of the RTD or thermocouple signal in the hazardous area of the field. After isolation, it is converted into a standard current signal output to the safety zone control system or other meter.
· Switch the thermocouple and thermocouple input signals according to different wiring methods. Input signal type or range can be configured via software.
· Output signal 4~20mA or 0~20mA.
· This product requires a separate DC power supply. Voltage-type magnetic isolation between power supply-input-output.
Model /Selection Table:
Option |
Model and code |
Description |
Basic model |
XSA-ZT |
Thermal resistance or thermocouple input isolation barrier (smart) |
Special function |
F |
Input line fault alarm, sensor fault alarm |
|
Default, no special function |
|
Channel form |
11 |
1 in 1 out |
12 |
1 in 2 out |
|
Input signal |
-U |
Thermal resistance (RTD) or thermocouple (TC) |
Output signal |
A |
4~20mA |
B |
0~20mA |
|
Z |
Special order |
|
Power supply voltage |
-V1 |
Power supply (terminal) 20~32VDC |
-V2 |
Power supply (rail) 20~32VDC (special power supply DIN rail required) |
|
Service Code |
-QC9A |
Product Service Code |
Selection example |
Technical data:
Size:
Width |
14.5mm |
Height |
102.6mm |
Depth |
124mm |
Housing Material / Color |
PC(Polycarbonate)+PPT Material / Black Gray |
Protection level |
IP20 |
Environmental conditions:
Ambient temperature |
-20~+60℃ |
Ambient temperature (storage or operation) |
-40~+80℃ |
Ambient humidity (operation) |
5~95%RH (no condensation) |
Input (intrinsically safe):
Available sensor type (RTD) |
Pt100, Cu50 and other thermal resistance |
Available sensor type (TC) |
K, E, S, B and other thermocouples |
Temperature measurement range |
Range depends on sensor type |
Output:
Current output |
4~20mA ; 0~20mA |
Maximum output current |
22mA(±1mA) |
Current output load |
Adaptive load 0~300Ω (factory default) |
Output ripple |
<10mV p-p |
Output status at sensor failure |
Output current <3.5mA (lower limit) or >21mA (upper limit) |
Power supply:
Rated supply voltage |
24VDC |
Power supply voltage range |
20~32VDC |
Maximum current consumption |
<45mA (1 in 1 out); <75mA (2 in 2 out) |
General parameters:
Standard accuracy |
Typical value±0.1%FS |
Zero migration range |
-10~100mV or0~385Ω |
Range migration range |
3.8~100mV or 12.8~400Ω |
Output resolution |
<3.8~100mV or 12.8Ω~400Ω range, 1μA |
Thermocouple input, cold junction compensation error |
±0.5~1℃ (compensation range -15~+75°C) |
Thermal resistance input, wire resistance effect |
Thermal resistance three-wire input (≤10Ω/line), <±0.005 %/Ω |
Load change effect |
±2μA |
Temperature drift |
· -10~35 mV range: 0.0005% or 0.6μV (whichever is larger) |
Power-on or storage time drift |
±2μA (180 days) |
Response time |
<10ms |
Power-on stabilization time |
<1s |
Maximum withstand voltage |
Input-output-power supply: 2500V AC RMS / 1 minute |
Protection parameters |
· Power-on shock protection, power-on slow start >20ms · Distribution protection, distribution output clamp current 28mA (±4mA) B. Input-output-power supply can withstand 2500V RMS/1 minute without damage. C. The short circuit or open circuit formed by the misconnection of the terminal is not damaged. |
Electromagnetic compatibility (EMC) |
in accordance with IEC 61326-1 (GB/T 18268), IEC 61326-3-1 |
LCD display or LED backlight indication |
· LCD display: input value and output value · LED backlight indication: Power on, the product model on the panel is clearly visible through the LED backlight perspective. |
Applicable occasions |
Installed in a safe place, can be connected with intrinsically safe equipment in Zone 0, Zone 1, Zone 2; IIC, IIB, IIA; T4~T6 danger zone |
Field device suitable for connection |
Thermal resistance or thermocouple temperature sensor, millivolt signal, transmitter or current source signal |
Mounting method |
Horizontal or vertical mounting, can be mounted on standard 35mm DIN rail (or dedicated busbar backplane powered DIN rail) |
Wiring parameters:
Rigid conductor cross section (min/max) |
0.5mm²/2.5mm² |
Flexible conductor cross section (min/max) |
0.5mm²/2.5mm² |
Minimum Conductor Cross Section (AWG)) |
24 |
Maximum Conductor Cross Section (AWG) 14 |
14 |
Stripping length |
7mm |
Connection type |
M3 screw fastening connection |
Screw torque |
Up to0.6Nm |
Explosion-proof parameters:
Maximum safety voltage (Um) |
250VAC/DC |
Maximum output voltage (Uo) |
7.2VDC |
Maximum output current (Io) |
8.68mA |
Maximum output power (Po) |
15.62mW |
Maximum external inductance (Lo) |
5mH |
Maximum external capacitance (Co) |
6μF |
Certification/Standards:
CE certification |
in line with CE standards |
National Explosion-proof Electrical Product Quality Supervision and Inspection Center (CQST) certification |
[Ex ia Ga] IIC conforms to GB 3836.1, GB 3836.4, GB 3836.20 |